1S4359128INSTALLATION INSTRUCTIONSIMPORTANT PagePlease Read Before Starting1. GENERAL...31-
10S43591283-5. Checking the DrainageAfter wiring and piping are completed, use the follow-ing procedure to check that the water will drainsmoothly. Fo
11S4359128Safety stringAir filter0150_X_I45°Fig. 3-13Ceiling panelAir intake grilleLatch0149_X_IScrew Ceiling PanelNever touch or attempt tomove the
12S4359128NOTE NOTE0967_X_ICeiling panelCeiling panelMarkScrews M5 with washerCeiling panel wiringconnector Air filterAir-intake grillePanel catch (pu
13S43591283-9. Duct for Fresh Air● Air-intake chamber (including Duct connection box and flange) are attached to the indoor unit when used totake fres
14S4359128(b) INSTALLING THE AIR-INTAKE CHAMBER● Set the air-intake chamber to the indoor unit takingcare not to set to the incorrect direction. (Fig.
S4359128154. How to Install the Remote Control Unit Wireless Remote Control UnitThe remote control unit can be operated from either anon-fixed positi
16S4359128 Wired Remote Control Unit (Option)(1) To access the printed circuit board, remove thecover plate of the electrical component box.(2) Attac
S4359128175. Address SwitchesIf you are installing one indoor unit or one group ofindoor units in the same room, it is necessary for youto assign each
18S43591286. Electrical Wiring6-1. General Precautions on Wiring(1) Before wiring, confirm the rated voltage of the unitas shown on its nameplate, the
S435912819● Conduit's trade size for this unit is 1/2". Theconduit can be purchased at a hardware store.● The fuse located in the outdoor un
2S4359128When Transporting……………………………………………………………………Be careful when picking up and moving the indoor andoutdoor units. Get a partner to help, and bend
20S4359128Loose wiring may cause theterminal to overheat or resultin unit malfunction. A firehazard may also exist.Therefore, ensure that allwiring is
S4359128217. How to Process TubingThe narrow tubing side is connected by flare nut, andthe wide tubing side is connected by brazing.7-1. Use of the Fl
22S43591287-4. Precautions during Brazing● Replace air inside the tube with nitrogen gas toprevent copper oxide film from forming during thebrazing pr
S435912823Because capillary tubing is installed in the outdoor unit,both the wide and narrow tubes of this air conditionerbecome cold. Therefore, to p
24S4359128CAUTION8. Air PurgingAir and moisture remaining in the refrigerant system haveundesirable effects as indicated below. Therefore, theymust be
S435912825(5) With the vacuum pump still running, close the “Lo”knob of the manifold valve. Then stop the vacuumpump.(6) With the accessory hex wrench
26S43591289. Test Run9-1. Performing Test RunBe careful since the fan willstart when performing TestRun.(1) The Operation Selector is located on the e
S4359128279-3. Basic Function of the Service ValvesThe basic function of the service valves are given in Table 7 below.ActionNarrow Tube Service Wide
3S43591281-3. Optional Copper Tubing KitCopper tubing for connecting the outdoor unit to theindoor unit is available in kits which contain the narrowa
4S43591281-7. Tubing Length● Refrigerant tubing between the indoor and outdoorunits should be kept as short as possible.● Select and decide the instal
5S43591282. Selecting the Installation Site Indoor UnitAVOID:● areas where leakage of flammable gas may beexpected.● places where large amount of oi
6S4359128Out-doorunitHeat sourceHot airExhaust fan1817_C_INOFig. 2-2Min.7 ft.(2 m)Min.7 ft.(2 m)Min. 6 in. (15 cm)Air intakeGroundObstacleObstacle abo
7S4359128Fig. 3-1Fig. 3-2Hole-in-anchorHole-in-plugConcrete InsertSuspension bolt (M10 or 3/8")(field supply)0038_T_IFig. 3-30962_S_IA (ceiling o
8S43591283-3. Placing the Unit Inside the Ceiling(1) When placing the unit inside the ceiling, deter-mine the pitch of the suspension bolts using thes
9S43591283-4. Installing the Drain Piping(1) Prepare standard hard PVC pipe (O.D. 1-3/64 in.)for the drain and use the supplied drain hose andhose ban